Industrial PC, a Fan-less cooling and smallest case allows for space-saving design, so it can be placed horizontally or vertically to offer you best placement options, and you`ll set it on a desk and forget its even there.
Low cost mini pc, Personal computer, Miniconputer, Industrial PC, Mini pc windows Shenzhen Innovative Cloud Computer Co., Ltd. , https://www.xcycomputer.com
GCK Series Drawout Type Low Pressure Voltage Switch Board are used forElectric motoring  control system, and power distributing center. They are applied toPower stations, electric substations, buildings, edifices, airports, hospitals,Industrial and mining establishments as three-phase 50Hz, voltage 380V and as follow electric system suited for the electricity, the feed, the lighting,The motor control and the power compensate. It conforms to the GB7251-97,ZBK36001-89 and IBC439-1 standards.
Product advantage
The series has high breaking capacity, dynamic thermal stability, advanced structure, reasonable, practical electric scheme, series resistance, versatility, any combination of program modules, a cabinet to accommodate the loop more, save area, beautiful appearance, high degree of protection, safe, reliable, easy maintenance, etc.
Using Condition:
Â
1. General Temperature: Not over than +40, Not less than -5. Equal Temperature35.
2. Altitude height not over than 1000M
3. Relative Humidity=90% (+25)
4. Earthquake frequency not over 8 degree
5. Without dust, fire, Corrosion or other dangerous items around
technical parameters
Â
Rated frequency(HZ)
50
Rated working voltage(V)
380Â 630
Rated insulation voltage(V)
750
Rated current(A)
The level of bus
630-3150
Vertical Bus
600
Rated short time withstand current
The level of bus
  80KA(RMS) 1 second
Vertical Bus
  50KA(RMS) 1 second
  When the rated peak withstand current
The level of bus
  176KA
Vertical Bus
  110KA
   Main circuit connector(A)
  63,200,400
   Auxiliary circuit connector(A)
  10
   One minute power frequency withstand  voltage(V)
  2500
   The maximum capacity of the motor  control(KW)
  155
   Operation
  Locally, remote, automatic
              Dimensions                Â
                 H  * W * D  PC.MCC cabinet after qualifying
  2200x600x1000(800)
  MCC cabinet the right cable outlet chamber
  2200x800x500
  PC.MCC cabinet or cabinet Right after qualifying
  2200x800x1000(800)
  PC line counters and Liaison Cabinet
  2200x1000(800)x1000